S.I.C.E.S. S.R.L.

D-PRO protection relay

D-PRO

Multifunction protection relay for genset

Icon

8 x Digital inputs

Icon

4 x Digital outputs

Icon

Ethernet connection

Icon

CANBUS Protocol

Icon

USB Port

Icon

RS232

Icon

RS485

Icon

History logs

Description

Multifunction protection relay used to provide additional generator protections in more demanding applications, such as medium or high voltage plants, or oil & gas installations.

D-PRO is studied in order to expand functions and protections already included in the DST4602Evolution genset controller, enhancing its performances:
it provides a can bus connection for direct communication with it. All the D-PRO measurements and alarms are shown on the display of DST4602Evolution, and the relay’s protections are directly managed by the genset controller.

Alternatively, it can be used stand-alone, connecting to the external control systems by its digital inputs and outputs.
This device has been designed to be placed in a control panel and can be configured/monitored through the different available communication ports.
Parameters settings is directly managed by the free programming tool BOARDPRG3.

Further details

A comprehensive configurable history logging system is available, recording data on events and periodically (832 recordings for each archive with the default configuration).

Additional pre-trigger and post-trigger fast recording allows to check what happened just before and/or just after the trip of a protection (112 recordings with the standard configuration). History logs can be visualized using the HISVIEW PC software.

Four alternative configuration (selectable by digital inputs) are available, providing support to multi-voltage and/or multi-frequency panels.

Digital inputs can be configured to selectively enable or disable groups of protections, allowing an easy integration in existing panels. Additional protections can be added by means virtual analogue inputs.

Configurable AND/OR logics are available for the digital outputs configuration, allowing remote signalling of the trip of the protections. Specific output functions are provided for the management of the interface and back-up circuit breakers.

Overall dimensions in both versions

Inputs and outputs

  • 8 programmable digital inputs.
  • 4 programmable relays (maximum 10A @ 250Vac each).
  • 7 currents measurement inputs for external current transformers, double internal scaling system 5A or 1A.
  • 1 current measurement input for external tore transformer.
  • 1 three-phase four-pole voltage sensor (L1-L2-L3-N), double internal scaling system 400V (or 100V with specific option).
  • 1 voltage input maximum 100V for the 59N protection.
  • 8 signalling LEDs.

Communication

  • 8 programmable digital inputs.
  • 1 USB port (Modbus RTU slave).
  • 1 RS232 port (Modbus RTU slave).
  • 1 RS485 insulated port (Modbus RTU slave).
  • 1 Ethernet port RJ45 (Modbus TCP slave).

Protections for renewable sources
ANSI/IEEE codes

  • 27 Under voltage.
  • 27T Time-depending under voltage.
  • 32P Maximum active power.
  • 32R Active power reverse.
  • 32Q Maximum reactive power.
  • 40 Loss of field.
  • 46 Maximum negative sequence current.
  • 47 Phase sequence.
  • 50 Instantaneous over current.
  • 51 Time-depending over current.
  • 50N Instantaneous neutral over current.
  • 51N Time-depending neutral over current.
  • 50V Voltage restrained instantaneous over current.
  • 51V Voltage restrained time-depending over current.
  • 59 Over voltage.
  • 59N Residual overvoltage.
  • 64 Restricted earth fault.
  • 81O Over frequency.
  • 81U Under frequency.
  • 87G Differential protection.
  • Power supply voltage: 7...32Vdc.
  • Power consumption in stand-by: less than 5 W (200mA @ 27 VDC).
  • Rated frequency: 50Hz or 60Hz
  • Operating temperature: -30°…+70 °C.
  • Storage temperature: -40…+80 °C.
  • Humidity: 10-90% (non-condensing).
  • Dimensions: 244 (L) x 178 (H) x 40 (P) mm.
  • Weight: 600gr .
  • Protection degree: IP20
  • EMC: compliant to EN61326-1.
  • Safety: compliant to EN61010-1.

Commercial datasheets

For more information

Compila i campi richiesti.
Compila i campi richiesti.
Compila i campi richiesti.
Compila i campi richiesti.
Compila i campi richiesti.
© 2023 S.I.C.E.S. Società Italiana Costruzioni Elettriche Sumirago S.R.L.
Via Molinello n. 8/B 21040 - JERAGO CON ORAGO (VA) | Tel. +39 0331212941 | Fax +39 0331216102
Codice Fiscale, Partita IVA e N. Iscrizione al Registro Imprese CCIAA di Varese 00587340126 R.E.A. CCIAA di Varese 142977 VAT Number IT00587340126 Capitale Sociale € 500.000 i.v.

Design & programming Graphic studio VLADO
Cookie Policy | Privacy Policy | DURC | Politica SGI | IMS Policy